Interim Life Safety Measures (ILSM)
Temporary safeguards (extra fire watches, additional portable extinguishers, alternate egress routes, staff notification and drills) put in place whenever construction temporarily knocks out part of a healthcare facility's normal fire or life safety protection, such as a disabled fire alarm zone or a blocked exit corridor, required by the Joint Commission for accreditation.
Why it matters
A hospital can't simply accept reduced fire protection while a project is underway, patients may not be able to evacuate quickly on their own. ILSM is the formal, documented substitute for whatever protection construction temporarily removes, so the facility stays genuinely safe, not just technically under renovation.
On a real project
A renovation requires temporarily shutting down a corridor's sprinkler zone for a tie-in. The ILSM plan adds continuous fire watch patrols with portable extinguishers in that corridor for the entire shutdown, documented and reviewed daily, until the sprinkler zone is restored and tested.
Who this matters most to
A Healthcare Construction Manager manages ILSM compliance whenever construction affects a facility's egress or fire protection, coordinating directly with the hospital's life safety and facilities staff. The fire marshal reviews and signs off on the ILSM plan before work affecting fire protection is allowed to proceed.
Where this goes wrong
A contractor disables a fire alarm zone for a tie-in and assumes the posted fire watch covers it, but the fire watch patrol gets pulled onto an unrelated task for an hour without a documented handoff. If an actual fire started during that gap, nobody would have caught it early, exactly the scenario ILSM documentation exists to prevent through a continuous, accountable chain of coverage.